Panasonic FPS Series User Manual page 187

Table of Contents

Advertisement

Communication
Adjusting the response time of the external device (when using FPG-COM4)
The RS485 port of FPG-COM4 occupies the communication line for a certain period of time
after sending data. During this time, data cannot be received from another device. Therefore,
the connected device should not send a response to the FPΣ before the time t indicated below
has passed.
FPG-COM4
External device
1
t
Response time
Baud rate
Response time
19200bit/s
t > 1ms
115200bit/s
t > 200μs
Make the following adjustments depending on the communication mode and the connected
device:
1. FPΣ using FPG-COM4:
PLC Link: No adjustments required.
-
Program controlled: Adjust t in the program algorithm.
-
MEWTOCOL-COM Master/Slave: Adjust t using the SYS1 instruction (see above)
-
2. Other PLCs from Panasonic:
PLC Link: Adjustment not possible.
-
Program controlled: Adjust t in the program algorithm.
-
3. Computer:
Adjust t in the program algorithm using a WAIT instruction.
-
4. Others:
Information about the time t (time after which the device starts to respond when
-
data has been received) can be obtained from the device manufacturer.
KT temperature controllers and inverters (e.g. VF-7E, VF-8X) can be used without
-
any adjustments because t ≥ 1ms.
GT Series terminals cannot be used.
-
170
t
Send data
Send response
t
FPΣ User's Manual