8.6.7 1:N Communication

The FPΣ and the external units are connected using an RS485 cable. Using the protocol that
matches the external units, the F159_MTRN instruction is used to send and receive data.
Data registers (DT)
Data to be sent
Data received
PLC
Data is received in receive buffer
The RS485 port of FPG-COM4 occupies the communication line for a certain period of time
after sending data. During this time, data cannot be received from another device. Therefore,
the connected device should not send a response to the FPΣ before the time t indicated below
has passed.
Baud rate
Response time
19200bit/s
t > 1ms
115200bit/s
t > 200μs
System register settings
By default, the COM port is set to MEWTOCOL-COM mode. For 1:N program controlled
communication, the system registers should be set as shown below.
Settings for COM port 1 (FPG-COM3, FPG-COM4)
No.
Name
412
COM port 1 - communication mode
413
COM port 1 - communication format
415
COM port 1 - baud rate
416
COM port 1 - receive buffer starting address
417
COM port 1 - receive buffer capacity
*)
The setting must match the external device connected to the communication port.
NOTE
When the RS485 port (COM port 1) of FPG-COM4 is used, set the baud rate
in the system registers to either 19200bit/s or 115200bit/s. Set DIP switch
SW1-2 of the cassette to the same setting (see page 162).
Data is sent using F159_MTRN
*)
*)
8.6 Program Controlled Communication
RS485
Set value
Program controlled
Data length:
7 bits/8 bits
Parity:
None/Odd/Even
Stop bit:
1 bit/2 bits
End code:
CR/CR+LF/None/ETX
Start code:
No STX/STX
2400–115200bit/s
0–32762 (initial value: 0)
0–2048 words (initial value: 2048 words)
221