8.7.5 Monitoring

When using a PLC link, the operation status of the links can be monitored using the relays
below. In FPWIN Pro, choose Monitor → Special Relays and Registers → PLC Link
Status to view the status of each relay.
To monitor other PLC link status items, such as the transmission cycle time and the number of
times that errors have occurred, choose Monitor → PLC Link Status in FPWIN Pro.
Remote programming of other linked PLCs is not possible.
NOTE
To access special data registers and special internal relays, use the PLC-
independent system variables.
Transmission assurance relays
For PLC link 0: R9060 to R906F (correspond to station no. 1 to 16)
For PLC link 1: R9080 to R908F (correspond to station no. 1 to 16)
Before using the data from a different station in the network, check to make sure the
transmission assurance relay for this station is TRUE.
Relay no.
Station no.
R9060
1
R9061
2
R9062
3
R9063
4
R9064
5
R9065
6
R9066
7
R9067
8
R9068
9
R9069
10
R906A
11
R906B
12
R906C
13
R906D
14
R906E
15
R906F
16
System variable name
sys_bIsPlcLink0Station1Active
sys_bIsPlcLink0Station2Active
sys_bIsPlcLink0Station3Active
sys_bIsPlcLink0Station4Active
sys_bIsPlcLink0Station5Active
sys_bIsPlcLink0Station6Active
sys_bIsPlcLink0Station7Active
sys_bIsPlcLink0Station8Active
sys_bIsPlcLink0Station9Active
sys_bIsPlcLink0Station10Active
sys_bIsPlcLink0Statio11Active
sys_bIsPlcLink0Station12Active
sys_bIsPlcLink0Station13Active
sys_bIsPlcLink0Station14Active
sys_bIsPlcLink0Station15Active
sys_bIsPlcLink0Station16Active
8.7 PLC Link
Conditions for TRUE/FALSE
TRUE:
• if the PLC link is normal
FALSE:
• if transmission has been
stopped, or
• if a problem has occurred, or
• if a PLC link is not being used
233