Initializing Parameter Settings (Fn005) - YASKAWA Σ-V Series User Manual

Ac servo drives; linear motor command option attachable type
Hide thumbs Also See for Σ-V Series:
Table of Contents

Advertisement

6 Utility Functions (Fn
6.6

Initializing Parameter Settings (Fn005)

This function is used when returning to the factory settings after changing parameter settings.
Follow the steps below to initialize the parameter setting.
Step
1
2
3
4
6-14
)
• Be sure to initialize the parameter settings while the linear servomotor power is OFF
• After initialization, turn OFF the SERVOPACK power supply and then turn ON again
to validate the settings.
• The parameters of the option module will not be initialized. For information on how to
initialize the parameters of the option module, refer to the manual of the connected
option module.
Display Example
Turn OFF the SERVOPACK power supply and then turn it ON again to validate the new setting.
Keys
Press the
Key to view the main menu for the util-
ity function mode.
Use the
or
select Fn005.
Press the
execution display of Fn005.
Note:
If the display is not switched and "NO-OP" is dis-
played in the status display, change the following set-
tings. (Refer to 6.12.)
• If Write Prohibited is set in Fn010:
→ Cancel the Write Prohibited setting.
• If a servo ON command is input:
→ Send a servo OFF command.
Press the
During initialization, "Parameter Init" is blinking in
the display.
After the initialization is completed, "Parameter Init"
stops blinking and the status display changes as fol-
lows: "BB" to "DONE."
Note:
Press the
display returns to the Utility Function Mode main
menu.
Operation
Key to move through the list,
Key. The display is switched to the
Key to initialize parameters.
Key not to initialize parameters. The
.