For details on setting the communication parameters, see "Setting System Registers in PROG
Mode" on page 110. For details on setting the link area, see "Link Area Allocation" on page
154.
NOTE
PLC Link is only available via the COM port.
For RS232C connections, the maximum number of stations is 2.
For PLC Link, the communication format and baud rate settings are fixed:
Data length: 8 bits
Parity:
Stop bit:
End code:
Start code:
Baud rate:
Station number setting for a PLC link
The station number can be set within a range of 1 to 16. For details on setting station
numbers,.
#1
#2
# Station number of PLC
A maximum of 16 stations can be connected in a PLC link
NOTE
Make sure the same station number is not used for more than one of the
PLCs connected through the PLC Link function.
Station numbers should be set sequentially and consecutively, starting
from 1, with no breaks between them. If there are fewer than 16 stations
linked, set the highest station number to reduce the link transmission cycle
time. See "Setting the Highest Station Number for a PLC Link" on page 160.
Odd
1 bit
CR
No STX
115200bit/s
#3
RS485
#4
Communication
#16
153