By default, the station number for each communication port is set to 1 in the system register
settings. There is no need to change this for 1:1 communication, but if 1:N communication is
used to connect multiple PLCs to the transmission line, the station number must be specified
to identify the different PLCs.
The station number is specified either by using
A. the SYS1 instruction
B. system register settings in the programming tool
The priority for setting the station number is in the above order.
REFERENCE
For details on the SYS1 instruction, please refer to your Programming Manual
or to the FPWIN Pro online help.
Baud rate
The default baud rate for most ports is 9600bit/s. Select a value from 2400 to
115200bit/s.
Lower baud rates of 300, 600, and 1200bit/s can be specified using the SYS1
instruction. However, this will not change the setting value of the system register.
The setting must match the external device connected to the communication port.
When using the RS485 port, a baud rate of 19200bit/s or 115200 bit/s is possible. Set
the baud rate in the system registers and set the DIP switch on the bottom of the unit
to the same setting. Confirm the baud rate setting before installation. The factory
setting is 115200bit/s.
19200bit/s
115200bit/s
RS485 baud rate switch
Unused
1
PLC Link: The baud rate is fixed at 115200bit/s.
FP0 compatibility mode:
TOOL port 9600 or 19200bit/s
COM port
300, 600, 1200, 2400, 4800, 9600, or 19200bit/s
Communication format setting
Default settings:
Data length: 8 bits
Parity:
Odd
Stop bit:
1 bit
End code:
CR
Start code:
No STX
1
1 2
Communication
111