4

Packing and Lifting

4.1

Unpacking

Unpack the circuit breaker and inspect it for damage.
If the circuit breaker or cradle is to be installed at a later date:
they may only be stored and redispatched in the original packing.
Equipment Damage.
Placing the circuit breaker on its rear side may cause damage to the finger cluster assemblies.
When handling circuit breakers, do not place them on their rear side.
4.2

Weights

Frame Size
Draw-out circuit breaker
3-pole
II 800 A
159 lb / 72 kg
II 1600 A
159 lb / 72 kg
II 2000 A
177 lb / 80 kg
II 3200 A
209 lb / 95 kg
II Fused
227 lb / 103 kg
III
260 lb / 118 kg
III Fuse
225 lb / 102 kg
Carriage
4 – 1
NOTICE
Fixed Mounted
Circuit Breaker
4-pole
4-pole
210 lb / 95 kg
185 lb / 84 kg
210 lb / 95 kg
185 lb / 84 kg
227 lb / 103 kg
203 lb / 92 kg
258 lb / 117 kg
229 lb / 104 kg
not available
not available
434 lb / 197 kg
375 lb / 170 kg
not available
not available
Weight
Cradle
3-pole
4-pole
112 lb / 51 kg
161 lb / 73 kg
112 lb / 51 kg
161 lb / 73 kg
128 lb / 58kg
181 lb / 82 kg
152 lb / 69 kg
212 lb / 96 kg
150 lb / 68 kg
not available
306 lb / 139 kg
410 lb / 186 kg
306 lb / 139 kg
not available
Circuit Breaker
+ Cradle
3-pole
4-pole
Only lift separately
Only lift separately
Only lift separately
Only lift separately
Only lift separately
Only lift separately
Only lift separately

Hide quick links: