Resetting The Bell Alarm With Reclosing Lockout (Optional) - Siemens UL 1066 Operating Instructions Manual

Low voltage power circuit breaker
Table of Contents

Advertisement

10.2

Resetting the Bell Alarm with reclosing lockout (optional)

WL circuit breakers are normally configured to be immediately ready to close again following a trip. With the automatic reset of the Bell
Alarm, the tripping solenoid is automatic resetting after the trip unit has tripped. The circuit breaker is immediately ready to close again. For
confirmation, the tripped indicator must be reset, either manually on the trip unit or via the remote reset solenoid.
When the WL breaker is configured with option WLNOAUTRSET, the tripping coil must be manually reset before the circuit breaker is
capable of closing. The following instruction details the resetting of the Bell Alarm, and the tripping coil.
1
Indicators
2
3
4
Indicators
5
Circuit breaker is tripped by the trip unit
Press Bell Alarm (red pin), until it latches
Bell Alarm reset
Circuit breaker is ready to close again if the closing spring is charged and no interlock is active.
Signals
Manual reset
F5
Tripping solenoid
Tripping solenoid and Bell Alarm are reset.
Trip
S24
Bell Alarm
X9.12
X9.14
X9.13
Reset
S24
X9.12
X9.14
X9.13
Bell Alarm
10 – 2