Replacing rating plug
Circuit breaker may trip.
If the trip settings are changed while the breaker is closed (and under load) the breaker may trip.
Adjust parameters only when the circuit breaker is in the open position.
9.1.9

Ground-fault protection modules

Various trip units can be optionally equipped with ground-fault protection modules. The following ground-fault protection modules cannot be
removed once they have been installed.
Depending on the ground-fault protection module version, the set value being exceeded will cause either an alarm only or an alarm and a
 (page 9-13)
trip at the same time.
The following device combinations are possible:
Trip unit
ETU745 - 748
ETU776
The following options exist for ground-fault detection:
- vectorial summation of the phase currents or vectorial summation of the phase currents and the neutral conductor current if a
neutral sensor is used
- Direct measurement of the ground-fault current using a separate 1200 A : 1 A ground-fault sensor
Input current carrying capacity of the ground-fault protection module:
- max. 1 A continuous
- max. 5 A for 0.5 sec.
Alarm and tripped signals can be transmitted via the c, PROFIBUS-DP and MODBUS.
Module GFM A 745
Changeover switch for ground-fault
detection
Rotary coding switch for ground-fault
alarm setting value
- Alarm only, circuit breaker does not trip
- The changeover switch for ground-fault detection is only accessible when the control panel or the trip unit itself is removed.
1
OPEN
Ground-fault protection module
GFM A 745-748
GFM AT 745-748
GFM A 776
GFM AT 776
NOTICE
3
2
Ground-fault alarm indicator
Rotary coding switch for ground-fault
2
delay setting t
/ I
t
g
g
9 – 45