Siemens UL 1066 Operating Instructions Manual page 132

Low voltage power circuit breaker
Table of Contents

Advertisement

Circuit breaker may trip.
If the trip settings are changed while the breaker is closed (and under load) the breaker may trip.
Adjust parameters only when the circuit breaker is in the open position.
Internal circuit breaker self-test with tripping
T
he test can be canceled
at any time by pressing CLEAR
1
Press and hold CLEAR
2
The flashing time corresponds to the long-time delay
3
Circuit breaker trips
4
Test OK
q Reclosing a circuit breaker trip-
5
ped by the trip unit (page 6-9)
9 – 52
1
Press and hold TEST
All indicators will light up one after other (from left to right or from top to bottom)
t
R
Circuit breaker does not trip
Test not OK
Test with handheld test device
- Check wiring between trip unit and tripping solenoid
- Test tripping solenoid
NOTICE
2
Running light
The flashing time deviates more than 10% from the set long-time
delay
t
R
Test not OK
Trip unit is defective, even if the circuit breaker trips
3
0075-01-02
Release both buttons at the same time