Labels; Circuit Breaker Frame Type Label; Type Label Circuit Breaker Frame - Siemens UL 1066 Operating Instructions Manual

Low voltage power circuit breaker
Table of Contents

Advertisement

2

Labels

2.1

Circuit breaker frame type label

(with terminal designations)
Charging Motor
1st Shunt Trip
X5-1 (-)
240
VAC
X6-13 (-)
X5-2 (+)
250
VDC
X6-14 (+)
Remote Close Coil
UVR
X6-7 (+)
120
VAC
X5-11 (-)
X6-8 (-)
125
VDC
X5-12 (+)
Siemens Industry, Inc., Fort Worth, TX 76155 USA
2.2

Type label circuit breaker frame

(1)
Maximum rated current
(2)
Max. rated operating voltages
(3)
Rated short-circuit breaking capacity
(4)
Manufacturing date
(5)
Instruction book & outline drawings
(6)
Max. rated short-time withstand current
(7)
Rated frequency
(8)
Certifications
2 – 1
2nd Shunt Trip
240
VAC
X9-1 (-)
VAC
250
VDC
X9-2 (+)
VDC
Remote Reset
120
VAC
X8-13 (-)
120
VAC
125
VDC
X8-14 (+)
125
VDC
Ready to Close Switch
UVR Switch
X6-5
240 VAC
X9-10
240 VAC
X6-6
4 A
X9-11
3 A
1st Shunt Trip Switch
Open Fuse Switch
X9-7
240 VAC
X9-5
240 VAC
X9-8
3 A
X9-6
5 A
Assembled in USA
52a 1st Aux. SW. 52b
X6-3
X6-11
X6-1
X6-9
X6-4
X6-12
X6-2
X6-10
52a 2nd Aux. SW. 52b
X5-5
X5-9
X5-3
X5-7
X5-6
X5-10
X5-4
X5-8
240 VAC ,
10 A / 125 VDC ,
0.5 A / 24 VDC ,
3A
(8)
LISTED
R
Low Voltage AC
Power Breaker Frame
(7)
12SZ
Frame Size:
2000A
Frequency
50/60 Hz
kA Symm.
254 / 508 V
Inst.
100
(6)
Short Time
85
kA Symm.
600V
Inst.
85
Short Time
85
(5)
Instr. Book &
Outline Dwg.:
WLOPMAN1
(4)
Mfg. Date
2003-10-21
ID-No.
31910220089
Bell Alarm
240 VAC
5 A
X9-12
X9-14
X9-13
0131-FW
(1)
(2)
kA
(3)
kA
(2)
kA
(3)
kA

Hide quick links: