Changing the communication parameters
The communication parameters of the COM16 module can be changed by writing the required parameters (baud rate, serial configuration
and MODBUS communication address) in data set 160.
Register
High/
Address
Low
dec
hex
40961
0xA001
-
40963
0xA003
LOW
40963
0xA003
HIGH
40964
0xA004
LOW
40964
0xA004
HIGH
40965
0xA005
-
40979
0xA013
-
40982
0xA016
-
40985
0xA019
LOW
40985
0xA019
HIGH
40986
0xA01A
-
40995
0xA023
LOW
40995
0xA023
HIGH
40996
0xA024
LOW
40996
0xA024
HIGH
40997
0xA025
LOW
40997
0xA025
HIGH
40998
0xA026
LOW
40998
0xA026
HIGH
40999
0xA027
LOW
9 – 66
Address: A000 hex, Registers: 39, Access: Read / Write
Description
Header; value 0x00 00 00 00
Reserved
MODBUS address
Basic type of MODBUS data
transfer
Reserved
Data in the cyclic profile of
MODBUS
Reserved
IP address of the BDA/BDA
PLUS
MODBUS transmission rate
(baud rate)
Parity
Reserved
Property byte (parity)
Property byte (MODBUS
transmission rate (baud
rate))
Reserved
Property byte (MODBUS
address)
Property byte (basic type of
MODBUS data transfer)
Reserved
Property byte (data in the
cyclic profile of MODBUS)
Reserved
Property byte (IP address of
the BDA/BDA PLUS)
Dataset 160 – communication parameters
Data
Source
Source
1
point
WL
VL
-
COM16
COM11
-
-
-
5
COM16
COM11
6
COM16
COM11
-
-
-
7
COM16
COM11
-
-
-
10
BDA
-
427
COM16
COM11
428
COM16
COM11
-
-
-
428
COM16
COM11
427
COM16
COM11
-
-
-
5
COM16
COM11
6
COM16
COM11
-
-
-
7
COM16
COM11
-
-
-
-
BDA
-
Source
Length
Format
2
VL
(Bit)
COM21
-
32
-
-
8
unsign
COM21
8
ed char
COM21
Hex
2
-
-
8
Format
COM21
224
(7)
-
-
48
Format
-
40
(10)
Format
COM21
8
(427)
Format
COM21
8
(428)
-
-
144
COM21
PB
8
COM21
PB
8
-
PB
8
COM21
PB
8
COM21
PB
8
-
PB
8
COM21
PB
8
-
PB
8
-
PB
8
Scaling
-
-
0
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-