Siemens UL 1066 Operating Instructions Manual page 155

Low voltage power circuit breaker
Table of Contents

Advertisement

Setpoints
The setpoint function can be used to signal or record special events in the power system.
Parameter
Phase overcurrent
Ground overcurrent
Neutral overcurrent
phase current unbalance*
current demand
undervoltage
phase voltage unbalance*
overvoltage
overpower in normal direction
KW reverse
KW demand
KVA demand
KVAR demand
KVAR consumed
KVAR delivered
KVA
overfrequency
underfrequency
underpower factor (PF)
overpower factor (PF)
current THD
voltage THD
crest factor
form factor
1)
ANSI definition:
Ratio of the largest difference between the phases and the average of all 3 phases.
If one of these parameters exceeds or falls below its default settings, the trip unit is tripped after the adjusted delay via the c.
The parameters can be adjusted via:
- the test socket with the BDA
- the PROFIBUS-DP
- the MODBUS
- the graphical display (ETU776).
Range
30 - 10000 A
30 - 12000 A
30 - 10000 A
5 - 50%
30 - 10000 A
100 - 1100 V
5 - 50%
100 - 1100 V
1 - 12000 kW
1 - 12000 kW
1 - 12000 kW
1 - 12000 kVA
1 - 12000 kVar
1 - 12000 kVar
1 - 12000 kVar
1 - 12000 kVA
40 - 70 Hz
40 - 70 Hz
-0.001 - 0.001
-0.001 - 0.001
3 - 50%
3 - 50%
1 - 2.55
1 - 2.55
Delay
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
0 - 255 sec.
9 – 75