Gas Supply; Power Supply; Circulation Pump - Baxi POWER HT+ Series Installation And Service Manual

Gas fired floor-standing condensing boiler
Hide thumbs Also See for POWER HT+ Series:
Table of Contents

Advertisement

5 Before installation
Tab.10 Water flow rates in the boiler
Unit
Minimum flow rate
Litres/hour
Working flow rate
Litres/hour
with the low-loss
header kit
Fig.13
Pressure drops for POWER HT+
1.50
12
10
8
2
6
4
3
2
0
1
24

5 5 .2.2 Gas supply

5.2.3 Power supply

Power supply voltage

5.2.4 Circulation pump

The boiler's water flow rates must be higher than or equal to the specifica­
tions in the table below.
POWER HT+ 1.50
800
2450
5
4
MW-3000007-01
Before mounting, check that the gas meter has sufficient capacity (in
3
m
). To do this, you should bear in mind the consumption of all applian­
ces.
If the capacity of the gas meter is too low, inform the gas supply compa­
ny.
The boilers are designed to run on natural gas G20 and can be conver­
ted to run on G25 or G31 gas.
Note
To use a gas type other than natural gas (G20, G25) or LPG gas
(G31), contact an accredited assistance service.
Caution
Respect the polarities shown on the terminals: live (L), neutral (N)
and earth (
)
POWER HT+ 1.70
1500
3500
Note
ΔT: Temperature difference between the flow water and the return
water in the boiler
1 Q flow rate (litres/hour)
2 H pressure in metres of water column (mWC)
3 Operating water flow rate at nominal heating flow rate = 1330 litres/
hour where ∆T = 30°C
4 Operating water flow rate at nominal heating flow rate = 2000 litres/
hour where ∆T = 20°C
5 Operating water flow rate at nominal heating flow rate = 2660 litres/
hour where ∆T = 15°C
230 V AC/50 Hz
POWER HT+ 1.90
POWER HT+
1.110
2000
2250
4600
4800
7609474 - v02 - 04092014