5 Before installation
Tab.10 Water flow rates in the boiler
Unit
Minimum flow rate
Litres/hour
Working flow rate
Litres/hour
with the low-loss
header kit
Fig.13
Pressure drops for POWER HT+
1.50
12
10
8
2
6
4
3
2
0
1
24
5 5 .2.2 Gas supply
5.2.3 Power supply
Power supply voltage
5.2.4 Circulation pump
The boiler's water flow rates must be higher than or equal to the specifica
tions in the table below.
POWER HT+ 1.50
800
2450
5
4
MW-3000007-01
Before mounting, check that the gas meter has sufficient capacity (in
3
m
). To do this, you should bear in mind the consumption of all applian
ces.
If the capacity of the gas meter is too low, inform the gas supply compa
ny.
The boilers are designed to run on natural gas G20 and can be conver
ted to run on G25 or G31 gas.
Note
To use a gas type other than natural gas (G20, G25) or LPG gas
(G31), contact an accredited assistance service.
Caution
Respect the polarities shown on the terminals: live (L), neutral (N)
and earth (
)
POWER HT+ 1.70
1500
3500
Note
ΔT: Temperature difference between the flow water and the return
water in the boiler
1 Q flow rate (litres/hour)
2 H pressure in metres of water column (mWC)
3 Operating water flow rate at nominal heating flow rate = 1330 litres/
hour where ∆T = 30°C
4 Operating water flow rate at nominal heating flow rate = 2000 litres/
hour where ∆T = 20°C
5 Operating water flow rate at nominal heating flow rate = 2660 litres/
hour where ∆T = 15°C
230 V AC/50 Hz
POWER HT+ 1.90
POWER HT+
1.110
2000
2250
4600
4800
7609474 - v02 - 04092014