Adapting To Another Gas Type - Baxi POWER HT+ Series Installation And Service Manual

Gas fired floor-standing condensing boiler
Hide thumbs Also See for POWER HT+ Series:
Table of Contents

Advertisement

Tab.25 Checking and setting values for gas type G25
Diameter of the Venturi
Diameter of the nozzles
Minimum CO
(1)
2
Maximum CO
(1)
2
Maximum CO
Tab.26 Checking and setting values for gas type G31
Diameter of the Venturi
Diameter of the nozzles
Minimum CO
(1)
2
Maximum CO
(1)
2
Maximum CO
Fig.68
Removing the connection pipe
A
2
7609474 - v02 - 04092014
U U nit
POWER HT+ 1.50
mm
24
mm
4.20 (no. 2)
%
8.5
%
8.9
ppm
< 250
Unit
POWER HT+ 1.50
mm
24
mm
2.95 (no. 2)
%
9.5
%
10
ppm
< 250
B
2
POWER HT+ 1.70
30
Variable mixer
nozzles: top part
with a diameter of
5.70 mm, bottom
part with a diame­
ter of 6.50 mm.
8.6
8.9
< 250
POWER HT+ 1.70
30
4.0 (no. 2)
9.5
10
< 250

7.4.6 Adapting to another gas type

Caution
Only a fully trained, qualified professional may carry out the follow­
ing operations.
The boiler is pre-set in the factory to run on natural gas H H (G20).
Conversion kits are available for other types of gas G G 25 and G G 31.
1. Close the mains gas valve.
2. Remove the pipe connecting the Venturi to the gas valve.
Tab.27 Connection differences
Reference
A
B
POWER HT+ 1.90
POWER HT+ 1.110
34
38
6.30 (no. 2)
Variable mixer noz­
zles: top part with a
diameter of 6.80
mm, bottom part
with a diameter of
7.70 mm.
8.6
9.0
8.8
9.1
< 250
< 250
POWER HT+ 1.90
POWER HT+ 1.110
34
38
4.5 (no. 2)
5.0 (no. 2)
9.9
9.5
10
10
< 250
< 250
Model
POWER HT+ 1.50
POWER HT+ 1.70
POWER HT+ 1.90
POWER HT+ 1.110
7 Commissioning