7 7 .4.3 Setting the air/gas ratio (reduced thermal flow rate)

MW-3000046-01
1. Unscrew the left-hand plug, which corresponds to the flue gas
measurement point connection.
2. Connect the flue gas analyser to the connection on the left.
Note
Ensure that the opening around the sensor is completely sealed
when taking measurements.
Insert the sensor into the flue gas measurement point opening
to at least 8 cm for POWER HT+ 1.50 and POWER HT+ 1.70.
Insert the sensor into the flue gas measurement point opening
to at least 9 cm for POWER HT+ 1.90 and POWER HT+ 1.110.
3. Set the boiler's thermal flow rate to 0%.
See
Using the boiler according to thermal output, page 94
4. Measure the percentage of CO
5. Compare the values measured with the set point values in the Con­
trol and setting values table.
See
CO2 checking and setting values, page 62
Note
A tolerance of +/- 0.5% is acceptable.
6. If necessary, adjust the air/gas ratio using the OFFSET adjustment
screw.
See
Gas valves, page 62.
Note
Turn the gas adjustment screw clockwise to increase the CO
content.
Turn the gas adjustment screw counter-clockwise to reduce the
CO
content.
2
Note
A tolerance after adjustment of +/- 0.2% is acceptable, when the
front door is removed.
7 Commissioning
in the flue gases.