9 Settings
P P arameter
Parameter
number
5931
S S ensor input BX2
5932
S S ensor input BX3
5970
F F unction input H4
5971
C C ontact type H4
5973
F F requency value 1
H4
5974
F F unction value 1 H4
5975
F F requency value 2
H4
5976
F F unction value 2 H4
80
Description
None : No function on the sensor input.
Hot water sensor B31 : Sensor in the bottom section of the DHW
tank.
Collector sensor B6 : Solar collector sensor.
HW circulation sensor B39 : Circulation / DHW preparation sensor.
Buffer sensor B4 : Sensor in the top section of the storage tank.
Buffer sensor B41 : Sensor in the bottom section of the storage tank.
Flue gas temp sensor B8 : Flue gas sensor
Common flow sensor B10 : Common flow sensor (cascade).
Solid fuel boiler sensor B22 : Sensor for solid fuel boiler.
HW charging sensor B36
Buffer sensor B42 : Third sensor (in the middle) of the storage tank.
Common return sensor B73
Cascade return sensor B70 : Cascade return sensor.
Swimming pool sensor B13 : Swimming pool sensor.
Solar flow sensor B63 : Solar flow sensor for measuring efficiency.
Solar return sensor B64 : Solar return sensor for measuring efficien­
cy.
Primary exch sensor B26
See
Sensor input BX2
None : Default setting for boilers with DHW tank.
Flow measurement Hz : Default setting for instantaneous boilers.
Error/alarm message
NC
NO
Definition of parameters for collector specifications
Definition of parameters for collector specifications
Definition of parameters for collector specifications
Definition of parameters for collector specifications
Factory set­
ting
None
None
None
Error/alarm
message
15
20
162
120
7609474 - v02 - 04092014