Troubleshooting; Error Codes - Baxi POWER HT+ Series Installation And Service Manual

Gas fired floor-standing condensing boiler
Hide thumbs Also See for POWER HT+ Series:
Table of Contents

Advertisement

11 Troubleshooting

11 Troubleshooting

1 1 1.1 Error codes

Fig.
Error code
150
A
1 18
Error
118: Water pressure too low
0,4 bar
Display
10
1 1 0:Outside sensor
20
20:Boiler sensor 1
28
28:Flue gas temp sensor
40
40:Return sensor 1
50
50:HW sensor 1
52
52:HW sensor 2
73
73:Collector sensor 1
83
83:BSB short-circuit
84
84:BSB address collision
109
109:Boiler temp supervision
110
110:Lockout SLT
111
111:Shutdown limit thermost
117
117:Water pressure too high
118
118:Water pressure too low
125
125:Boiler temp too high
128
128:Loss of flame in op
130
130:Flue gas temp too high
133
133:Safety time exceeded
151
151:BMU internal
152
152:Parameterization
160
160:Fan speed threshold
171
171:Alarm contact 1 active
321
321:HW outlet sensor
343
343:Solar integration missing
384
384:Extraneous ligth
385
385:Mains undervoltage
386
386:Fan speed tolerance
116
566
B
Tab.63 List of error codes
C
A Error code
B Secondary error code
C Description of the error
Note
Press the
key to return to the main display.
MENU
The
symbol continues to be displayed on the control panel.
After one minute, if the error is not resolved, the error code is
displayed on the control panel a second time.
Description of the error
Outside temperature sensor
Flow back sensor
Flue gas sensor
Return sensor
Domestic hot water sensor (only for heating only models with
hot water tank)
Solar domestic hot water sensor (if incorporating a solar in­
stallation)
Solar collector sensor (if incorporating a solar installation)
Communication problem between boiler PCB and control
unit. Probable short circuit on the heating.
Address conflict between several control units (internal
anomaly)
Air present in the boiler circuit (anomaly)
Safety thermostat cut-off for overheating (pump blocked or
air in the heating circuit)
Safety thermostat cut-off for overheating
Pressure in hydraulic circuit too high
Pressure in hydraulic circuit too low
Safety cut-off for absence of circulation (check made by a
sensor)
Flame extinguished
Cut-off by flue gas sensor for overheating
Ignition error (4 attempts)
Internal error on heating PCB
General parameter setting error
Fan operation error
Error ACI board
Domestic hot water sensor damaged
General parameter setting error on the solar installation (if in­
corporating a solar installation)
Light incorrect (parasite flame — internal anomaly)
Power supply voltage too low
Fan threshold speed not reached