Tab.44 Menu W W ireless
Parameter
Parameter
number
120
B B inding
121
T T est mode
130
R R oom unit 1
131
R R oom unit 2
132
R R oom unit 3
133
O O utside temperature
sensor
134
R R epeater
135
I I n operation
140
D D elete all devices
Tab.45 Menus T T emps / mode CH1 – T T emps / mode CH2 – T T emps / mode CH3
Parameter number
Heating
Heating
Heating
circuit 1
circuit 2
circuit 3
714
1014
1314
720
1020
1320
730
1030
1330
732
1032
1332
740
1040
1340
741
1041
1341
742
1042
1342
746
1046
1346
750
1050
1350
7609474 - v02 - 04092014
Description
Activation of wireless connection with the base unit.
The test mode is used to check the wireless communication.
Checking the link.
Checking the link.
Checking the link.
Checking the link.
Checking the link.
Checking the link.
Deletes all appliances
Parameter
Description
F F rost protection
setpoint
H H eating curve
Heating curve gradient: The regulator calcu
slope
lates the flow T° set point which is used for the
control system, according to outside weather
conditions.
S S ummer/winter
Limit temperature for Heating/Frost Protection
heating limit
Mode switching. Triggers or shuts down the
heating in the course of the year according to
variations in outside T°. This switch is made
automatically in Automatic mode.
2 2 4-hour heating
The heating is shut down when the outside T°
limit
is equal to the room temperature + parameter
732 (deactivated in Comfort mode).
F F low temp
The flow set point calculated is limited by the
setpoint min
set value.
F F low temp
The flow set point calculated is limited by the
setpoint max
set value.
F F low temp
The set flow value is applied in room tempera
setpoint room stat
ture thermostat mode. ' ---' the boiler is running
in modulation mode.
D D elay heat
request
R R oom influence
Influence of the room T° and the outside T°
on calculating the flow temperature: ---%:
Simple regulation in accordance with outside
weather conditions
1...99%: Regulation in accordance with out
side weather conditions with room tempera
ture influence.
100%: Regulation in accordance with the
room temperature only.
9 Settings
Unit
Factory set
ting
°C
6
–
Heating
circuit 1:
1.5
Heating
circuit 2:
0.7
Heating
circuit 3:
0.7
20
°C
0
°C
25
°C
80
°C
80
%
50
75