Baxi POWER HT+ Series Installation And Service Manual page 76

Gas fired floor-standing condensing boiler
Hide thumbs Also See for POWER HT+ Series:
Table of Contents

Advertisement

9 Settings
P P arameter number
Heating
Heating
Heating
circuit 1
circuit 2
circuit 3
760
1060
1360
809
1109
1409
834
1134
1434
850
1150
1450
851
1151
1451
855
1155
1455
856
1156
1456
Tab.46 Menu T T emps / mode hot water
Parameter
Parameter
number
1600
O O perating mode
1610
H H ot water temp
setpoint
1612
R R educed temp
setpoint
1620
R R elease
76
Parameter
Description
R R oom temp
Cuts the heating circulation pump if the room T
limitation
° exceeds the current set point + parameter
760, 1060, 1360
C C ontinuous pump
No : The heating circuit / boiler pump may be
operation
shut down during an accelerated decline in
temperature or when the room temperature
set point is reached.
Yes : The heating circuit / boiler pump also
continues to run during the accelerated de­
cline in temperature and when the room tem­
perature set point is reached.
A A ctuator running
Setting the stroke of the servomotor on the
time
mixing valve used
F F loor curing
Controlled screed-drying function:
function
Off : The function is inoperative.
Curing/functional heating : Active for 7 days,
3 days at a T° of 25°C and 4 days at a T° of
55°C
Curing heating : Active for 18 days, 6 days
from 25°C to 55°C increasing by 5°C a day,
6 days at a T° of 55°C, 6 days from 55°C to
25°C diminishing by 5°C a day.
Functional/curing heating : First, "Functional
Heating" cycle, and then, "Ready for Occu­
pation".
Functional heating : First, "Ready for Occu­
pation" cycle, and then, "Functional Heating".
Manually : Regulation is based on the "Man­
ual Control Drying" set point.
F F loor curing setp
The flow temperature set point of the "Manual"
manually
controlled drying function can be set separately
for each heating circuit.
F F loor curing setp
Displays the current day of the controlled
current
screed-drying function. With ' ---' the function is
deactivated.
D D ays
Displays the current flow temperature set point
complete.current
of the controlled screed-drying function. With
' ---' the function is deactivated.
Description
Off Permanent running on the antifreeze set point
On DHW loading is done automatically at the nominal set point
EcoThe temperature maintenance function is deactivated
DHW set point during release times
Reduced set point outside release times
Start-up enabled:
Time hot water : This setting provides DHW preparation with a
dedicated timer program.
Time setting central heating : The release of DHW is done in //
of the period of occupation of the heating circuits.
24h/day : Default setting for instantaneous boilers.
Unit
Factory set­
ting
°C
0 0 .5
no
seconds
30
S
O O ff
°C
25
-
'---'
-
'---'
Factory setting
On
6 6 0°C
3 3 5°C
Time hot water
7609474 - v02 - 04092014