Chapter 4
Analog Input
In the single-ended modes, more electrostatic and magnetic noise couples
into the signal connections than in DIFF configurations. The coupling is the
result of differences in the signal path. Magnetic coupling is proportional
to the area between the two signal conductors. Electrical coupling is a
function of how much the electric field differs between the two conductors.
With this type of connection, the NI-PGIA rejects both the common-mode
noise in the signal and the ground potential difference between the signal
source and the device ground.
Refer to the
Floating Signal Sources
connections.
When to Use Referenced Single-Ended (RSE)
Connections with Floating Signal Sources
Only use RSE input connections if the input signal meets the following
conditions:
DIFF input connections are recommended for greater signal integrity for
any input signal that does not meet the preceding conditions.
In the single-ended modes, more electrostatic and magnetic noise couples
into the signal connections than in DIFF configurations. The coupling is the
result of differences in the signal path. Magnetic coupling is proportional
to the area between the two signal conductors. Electrical coupling is a
function of how much the electric field differs between the two conductors.
With this type of connection, the NI-PGIA rejects both the common-mode
noise in the signal and the ground potential difference between the signal
source and the device ground.
Refer to the
Floating Signal Sources
connections.
X Series User Manual
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Using Non-Referenced Single-Ended (NRSE) Connections for
section for more information about NRSE
The input signal can share a common reference point, AI GND, with
other signals that use RSE.
The input signal is high-level (greater than 1 V).
The leads connecting the signal to the device are less than 3 m (10 ft).
Using Referenced Single-Ended (RSE) Connections for
section for more information about RSE
4-14
ni.com