Facing Requirements - Lopi Pro Builder 72 Linear GSB2 Installation Manual

Table of Contents

Advertisement

Facing Requirements

Non-combustible facing must extend from the base of the fireplace to 35-1/2"(902mm) above the base of
the fireplace (see illustration below for details).
Non-combustible facing must extend the entire width of the unit to the framing opening on both sides.
Do not place facing over the glass opening.
Drywall (or other combustible) may be placed above the non-combustible facing (35-1/2"(902mm) above
the base of the fireplace). See illustration below for details.
WARNING: Do not place drywall or other combustibles over the front of the fireplace.
WARNING: Do not use adhesive to secure the facing. The high temperatures of the
fireplace may cause adhesives to emit odors. Use mastic or thin set (or other non-
combustible, non-odorous adherent) to attach the facing.
NOTE: Screws may be used to secure cement board or tile backer to the fireplace. Do not
penetrate the fireplace more than 1/2"(13mm).
1/8" (3mm) Gap
Make sure non-combustible board is cut and positioned so it maintains a 1/8" (3mm) gap from the tile
stop. This allows the fireplace structure to expand without cracking the facing (see dimensions below).
© Travis Industries
Installation
(for qualified installers only)
1/8" (3mm)
Framing Header
Minimum
72 Lin. = 77-1/8" 1959mm
11/9/20 - 1478
Minimum
10-3/8"
Minimum
264mm
35-1/2"
902mm
20-1/8"
512mm
Base of
Fireplace
PB 72 GSB2/GSR2 Aust.
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pro builder 72 linear gsr2

Table of Contents