Ul Standards Compliance For Dc Power Supply Input - YASKAWA GA800 Series Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800 Series:
Table of Contents

Advertisement

Drive Model
4007
4009
4012
4018
4023
4031
4038
4044
4060
4075
4089
4103
4140
4168
4208
4250
4302
4371
4414
4477
4568
4605
4720
*1
Class T fuses are fast-acting (non-time delay only).
*2
Yaskawa recommends a fuse with a larger rated current for cyclical load applications that frequently approach 150 % overload.

UL Standards Compliance for DC Power Supply Input

To comply with UL Standards, install a fuse for the DC power supply input.
Figure 5.11
shows a wiring example for a DC power supply that has two drives connected in parallel.
WARNING! Electrical Shock Hazard. Do not ground the main circuit bus. Incorrect wiring can cause serious injury or death.
YASKAWA SIEPC71061737B GA800 Drive Technical Reference
Semiconductor Fuse
Manufacturer: EATON/Bussmann
FWH-60B
FWH-60B
FWH-60B
FWH-80B
FWH-90B
FWH-150B
FWH-200B
FWH-200B
FWH-225A
FWH-250A
FWH-275A
FWH-275A
FWH-300A
FWH-325A
FWH-400A
FWH-500A
FWH-600A
FWH-700A
FWH-800A
FWH-1000A
FWH-1200A
FWH-1200A
FWH-1400A
FWH-1400A
Figure 5.11 Wiring Example for DC Power Supply Input
*2
5.3 UL Standards
Alternate Time-Delay
*1
Class CC, J, or T
Maximum Amp Rating
(Maximum SCCR (kA))
12 (100)
15 (100)
20 (100)
30 (100)
40 (100)
50 (100)
60 (100)
70 (100)
100 (100)
125 (100)
150 (100)
175 (100)
225 (100)
250 (100)
350 (100)
400 (100)
500 (100)
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable
Not applicable