External Power Supply Input Terminals; Serial Communication Terminals - YASKAWA HV600 Series Installation & Primary Operation

Ac drive for hvac fan and pump applications
Hide thumbs Also See for HV600 Series:
Table of Contents

Advertisement

10 Drive Start-Up Procedure
Type
Terminal
N.O. output
MA
(Fault)
Fault Relay
N.C. output
Output
MB
(Fault)
MC
Digital output common
M1
MFDO
(During Run)
M2
M3
MFDO
MFDO
(Zero Speed)
M4
M5
MFDO
(Speed Agree 1)
M6
Type
Terminal
MFAO 1
FM
(Output frequency)
MFAO 2
Monitor Output
AM
(Output current)
AC
Monitor common
External Power
+P
External power supply
Supply Output

External Power Supply Input Terminals

Refer to
Table 10.4
for a list of the functions of the external power supply input terminals.
Type
External Power Supply Input
Terminals

Serial Communication Terminals

Refer to
Table 10.5
for a list of serial communication terminals and functions.
Type
Serial Communication
58
Table 10.2 Control Circuit Output Terminals
Name (Default)
Table 10.3 Control Circuit Monitor Output Terminals
Name (Default)
Table 10.4 External Power Supply Input Terminals
Terminal
Name (Default)
PS
External 24 V power supply input
AC
External 24 V power supply ground
Table 10.5 Serial Communication Terminals
Terminal
Terminal Name
Communication
• APOGEE FLN communications
D+
input/output (+)
• BACnet communications
• MEMOBUS/ Modbus communications
• Metasys N2 communications
Use an RS-485 cable to connect the drive.
Communication
D-
output (-)
0 V
AC
Signal ground
FE
Option card ground
Drive Fault Signal Output
• Relay output
• 30 Vdc, 10 mA to 2 A
• 250 Vac, 10 mA to 2 A
• Minimum load: 5 V, 10 mA (Reference value)
Multi Function Digital Output
• Relay output
• 30 Vdc, 10 mA to 2 A
• 250 Vac, 10 mA to 2 A
• Minimum load: 5 V, 10 mA (Reference value)
Note:
Do not set functions that frequently switch ON/OFF to MFDO (M1 to M6) because this will
decrease the performance life of the relay contacts. Yaskawa estimates switching life at
200,000 times (assumes 1 A, resistive load).
Multi Function Analog Output
Select voltage or current output.
• 0 V to 10 V/0% to 100%
• 4 mA to 20 mA (receiver recommended impedance: 250 Ω)
Note:
Select with jumper switch S5 and H4-07 [Terminal FM Signal Level Select] or H4-08
[Terminal AM Signal Level Select].
0 V
Power supply for external devices.
• 24 V (150 mA maximum)
Supplies backup power to the drive control circuit, keypad, and option board.
21.6 VDC to 26.4 VDC, 700 mA
0 V
Function (Signal Level)
Note:
Set DIP switch S2 to ON to enable the
termination resistor in the last drive in an
APOGEE FLN, BACnet, MEMOBUS/ Modbus,
or Metasys N2 network.
YASKAWA TOEPC71061732E HV600 Drive Installation & Primary Operation
Function (Signal Level)
Function (Signal Level)
Function
• RS-485
• APOGEE FLN communications: 4.8 kbps
• BACnet communications: Maximum 76.8 kbps
• MEMOBUS/Modbus communications:
Maximum 115.2 kbps
• Metasys N2 communications: 9.6 kbps
-

Advertisement

Table of Contents
loading

Table of Contents