Auto-Tuning For Motor Parameters For Pm Motor - YASKAWA GA800 Series Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800 Series:
Table of Contents

Advertisement

4.8 Auto-Tuning
Input Data
Motor Base Frequency
Number of Motor Poles
Motor Base Speed
Encoder Pulse Count (PPR)
Motor No-Load Current
Motor Rated Slip Frequency
Motor Iron Loss
*4
Test Mode Selection
No-load voltage
*1
Input this value when A1-02 = 3 [Control Method Selection = Closed Loop Vector].
*2
Shows 0 Hz as the default value. If you do not know the Motor Rated Slip Frequency, keep the setting at 0 Hz.
*3
Input this value when A1-02 = 0 or 1 [Control Method Selection = V/f Control or V/f Control w/ PG].
*4
If T1-12 = 1 [Test Mode Selection = Yes], when you run the motor in Drive Mode for the first time after Auto-Tuning, the drive will
automatically set E2-02 [Motor Rated Slip] and E2-03 [Motor No-Load Current].
*5
Input this value when T1-10 [Motor Rated Slip Frequency] = 0 Hz.
*6
Set the same value to No-Load Voltage as T1-03 [Motor Rated Voltage] to get the same characteristics using Yaskawa 1000-Series drives
or other legacy models.

Auto-Tuning for Motor Parameters for PM Motor

This section gives information about Auto-Tuning for PM motors. Auto-Tuning sets these parameters:
• Motor parameters E1-xx, E5-xx
• Speed feedback detection uses F1-xx (only with CLV/PM)
Mode
PM Motor Parameter Settings
PM Stationary Auto-Tuning
PM Stationary Auto-Tuning for
Stator Resistance
Z-Pulse Offset (Pole Position)
192
Parameter
Unit
T1-05
Hz
T1-06
-
T1-07
min
T1-08
-
T1-09
A
T1-10
Hz
T1-11
W
T1-12
-
T1-13
V
Table 4.8 Auto-Tuning for PM Motors
Parameter Settings
Application Conditions and Benefits
• When the information from the motor test report or
motor nameplate is available.
T2-01 = 0
• Rotational/Stationary Auto-Tuning that energizes the
motor is not done. Manually input the necessary
motor parameters.
• When the information from the motor test report or
motor nameplate is not available.
Note:
T2-01 = 1
With Stationary Auto-Tuning, the energized drive
stays stopped for approximately 1 minute. During
this time, the drive automatically measures the
necessary motor parameters.
• After Auto-Tuning, the wiring distance between the
drive and motor changed by 50 m or more.
T2-01 = 2
• When the motor output and drive capacity are
different.
• When you do not know the encoder Z-pulse offset.
• When the encoder was replaced
• If you have compensated for the deviation from Z
T2-01 = 3
phase (Δθ).
Note:
The motor will rotate slowly while the drive
measures the encoder base position.
Rotational Auto-Tuning
(0)
x
x
-1
x
*1
-
-
*3
-
*6
YASKAWA SIEPC71061737B GA800 Drive Technical Reference
Auto-Tuning Mode
(T1-01 Setting)
Stationary Auto-Tuning
Line-to-Line Resistance
1
(1)
x
x
x
*1
x
*2
-
*5
*6
Applicable Control Method
(A1-02 Setting)
OLV/PM
AOLV/PM
(5)
(6)
x
x
x
x
x
x
-
-
(2)
-
-
-
-
-
-
-
-
-
CLV/PM
(7)
x
x
x
x