Set Mfai Terminal A3 To Ptc Input; Set Output Signals For Mfao Terminals Fm, Am - YASKAWA GA800 Series Technical Reference

Ac drive for industrial applications
Hide thumbs Also See for GA800 Series:
Table of Contents

Advertisement

3.6 Control I/O Connections
DIP Switch Settings
Terminal
Input Signal
Switch
Voltage input
A3
S1-3
Current input
Note:
• Set H3-02, H3-10 = 0 [Terminal A1 Function Selection, Terminal A2 Function Selection = Frequency Reference] to set A1 and A2 to
frequency reference. The drive will add the analog input values together to make the frequency reference.
• Use tweezers or a jig with a tip width of approximately 0.8 mm (0.03 in) to set DIP switches.
• Set DIP switch S4 to "AI" to use terminal A3 as an analog input (voltage/current) terminal. The default setting for DIP switch S4 is "AI".

Set MFAI Terminal A3 to PTC Input

Set terminal A3 as an MFAI or as the PTC input for motor overload protection.
Use DIP switch S4 to set the input function.
Terminal
A3

Set Output Signals for MFAO Terminals FM, AM

Set the signal type for terminals AM and FM to voltage or current output. Use jumper switch S5 and H4-07, H4-08
[Terminal FM Signal Level Select, Terminal AM Signal Level Select] to set the signal type.
104
Setting
No.
V
(Default)
H3-05
I
Figure 3.50 Location of DIP Switch S4
Settings for DIP Switches
AI
Functions as an MFAI terminal.
(Default)
Set H3-06 [Terminal A3 Function Selection] to select the input function.
Functions as the PTC input terminal.
PTC
Set H3-06 = E [Motor Temperature (PTC Input)].
Set S1-3 to "V" for voltage input.
Figure 3.51 Location of Jumper Switch S5
Parameter
0: 0 V to 10 V/0% to 100% (input impedance: 20 kΩ)
1: -10 V to +10 V/-100% to 100% (input impedance: 20 kΩ)
2: 4 mA to 20 mA/0% to 100% (input impedance: 250 Ω)
3: 0 mA to 20 mA/0% to 100% (input impedance: 250 Ω)