Switches and Jumpers on the Terminal Board

The terminal board has switches to adapt the drive I/Os to the external control signals as shown in
Set the switches to select the functions for each terminal.
Position
Switch
A
DIP switch S2
B
Jumper switch S5
DIP switch S1-1
C
DIP Switch S1-2
DIP switch S1-3
D
Dip switch S4
YASKAWA SIEPC71061737B GA800 Drive Technical Reference
Figure 3.46 Locations of Switches
Table 3.14 I/O Terminals and Switches Functions
Terminal
Enables and disables the MEMOBUS/Modbus communications
-
termination resistor.
FM, AM
Sets terminals FM and AM to voltage or current output.
A1
Sets the input signal type (voltage/current).
A2
Sets the input signal type (voltage/current).
A3
Sets the input signal type (voltage/current).
A3
Sets MFAI or PTC input.
Function
3.5 Control Circuit Wiring
Figure
3.46.
Default
OFF
FM: V (voltage output)
AM: V (voltage output)
V (voltage input)
I (current input)
V (voltage input)
AI (analog input)