Lifting Lug For Pipe Cabinets And Hoods; Lifting Detail For Unit Sizes 3 To 120; Lifting Lug Part Numbers - Trane CSAA Installation, Operation And Maintenance Manual

Performance climate changer air handlers indoor and outdoor units sizes 3 to 120
Hide thumbs Also See for CSAA:
Table of Contents

Advertisement

Installation - Mechanical
Figure 15. Lifting lugs for low-capacity and high-
capacity units
Width
Unit sizes 35-57
High capacity and
low capacity
Figure 16. Lifting lug for pipe cabinets and hoods
Pipe cabinet or hood
lifting lug
Figure 17. Lifting lug part numbers
Left-hand lug
Part# 495318810001
Right-hand lug
Part# 495318800001
26
Width
Height
Unit sizes 3-30
Diameter
Low capacity lifting lug
High-capacity lifting lug
Part# 495118900001
Table 9.
Lug hole dimensions for low-capacity (under
3000 lbs.) and high-capacity (3000 lbs and over)
units
Section
Location
Unit Size
Indoor
3-30
Indoor
35-57
Unit Lug
Hole Size
Indoor
66-120
Outdoor
3-30
Pipe Cabinet
Outdoor
3-120
Hood
Outdoor
3-120
For unit sizes 3 to 120 with integral base frame, use
field-provided spreader bars and slings to rig units and
subassemblies as shown in
is not designed to be lifted or rigged from the top of the
unit.
Figure 18. Lifting detail for unit sizes 3 to 120
Rigging and spreader
bars furnished
by others
For outdoor units, never stack the pipe cabinet or inlet
hood on the unit as it is being lifted.
Do not attach the intake/exhaust hood or pipe cabinet
to the unit prior to lifting the unit. Doing so may
damage the equipment. Attach the hoods to the unit
only after all sections are in place.
For outdoor air handlers, all shipping supports and
crating on the face of the sections must be removed to
permit proper fit-up and sealing of the surfaces.
Dispose of properly.
Width
Height
0.88
1.38
1.31
1.43
1.25
2.75
1.25
2.75
2.5-in. diameter
1-in. diameter
Figure
18. The air handler
CLCH-SVX07K-EN