Optional Damper Actuators; Optional Air Temperature Sensors; Cdq Motor Data; Cdq Motor Wiring - Trane CSAA Installation, Operation And Maintenance Manual

Performance climate changer air handlers indoor and outdoor units sizes 3 to 120
Hide thumbs Also See for CSAA:
Table of Contents

Advertisement

Installation - Electrical
If not factory-installed, the electrical contractor must
provide and install a starter or starting contactor,
disconnect, fuses, etc., as required by local codes, for the
CDQ wheel motor. Do not install a variable frequency
drive (VFD) to control the desiccant wheel speed. This

Optional Damper Actuators

Each actuator requires 24 Vac supply power and wiring for
the 2–10 Vdc control signal. This wiring should be sized

Optional Air Temperature Sensors

If not factory-wired, connection to the air temperature
sensors is made by penetrating through the side of the
module wall and making electrical connections to the
temperature sensor. Nominal resistance of these sensors
is 1,000 ohms at 32 degrees F (0 degrees C). The sensor is
Table 37. CDQ motor data
Wheel Size
(nominal cfm)
500-5000
6000-40,000
Note: *Motors are wired for counter-clockwise rotation
Figure 154. CDQ motor wiring
M
5000C 1 wheels and below
≤48 in. diameter
118
HP
Voltage/phase
1/80
115 Volt Single Phase
1/80
115 Volt Single Phase
Red
Black
Black
White
Green
may result in failure of the wheel motor. The motor
requires air movement for continuous operation.
Operating the wheel for long periods with the fan off may
result in motor failure.
and installed as required per national and local electrical
codes.
a thermistor with a platinum 375 resistance curve. This
wiring should be sized and installed as required per
national and local electrical codes.
HZ
Full Load Amps
60
0.3
60
0.3
Black
M
6000C1 wheels and above
≥54 in. diameter
Rotation RPM
Rotation Direction
2.30
CW/CCW*
4.50
CW/CCW*
Red
Black
White
Green
CLCH-SVX07K-EN