Energy Recovery Recirculation Parallel-Blade Damper; Face Damper Torque Requirements - Trane CSAA Installation, Operation And Maintenance Manual

Performance climate changer air handlers indoor and outdoor units sizes 3 to 120
Hide thumbs Also See for CSAA:
Table of Contents

Advertisement

Component Installation
Table 29. Energy recovery recirculation parallel-blade damper
Unit size
A (in)
3
16.00
4
28.50
6
28.50
8
35.00
10
46.00
12
51.00
14
56.50
17
56.50
21
64.50
25
64.50
30
78.00
35
84.50
40
97.00
50
110.00
Table 30. Face damper torque requirements
Unit size
A (in)
3
23.20
4
35.70
6
35.70
8
42.20
10
53.20
12
58.20
14
63.70
17
63.70
21
71.70
25
71.70
30
85.20
35
43.44
40
32.19
50
36.52
57
36.52
66
41.52
80
41.52
100
46.19
120
55.35
70
Damper
B (in)
qty
13.97
1
13.97
1
13.97
1
13.97
1
13.97
1
13.97
1
13.97
1
13.97
1
13.97
1
13.97
1
13.97
1
13.97
1
13.97
1
13.97
1
B (in)
Damper Qty
19.72
1
19.72
1
25.47
1
25.47
1
25.47
1
31.22
1
31.22
1
36.97
1
42.72
1
48.47
1
48.47
1
50.94
2
50.94
3
62.44
3
68.19
3
73.94
3
85.44
3
99.41
3
99.41
3
Torque
Actuator torque
(in-lb.)
(max) (in-lb.)
10.90
42.00
19.40
42.00
19.40
42.00
23.80
42.00
31.20
42.00
34.60
42.00
38.40
180.00
38.40
180.00
43.80
180.00
43.80
180.00
53.00
180.00
57.40
180.00
65.90
180.00
74.70
180.00
Torque (in-lb)
13.80
21.30
27.50
32.50
40.90
54.90
60.10
71.10
92.50
105.00
124.70
133.70
148.60
206.70
225.70
278.20
321.50
416.10
498.70
Actuator
qty
Linkage
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Actuator torque
(max) (in-lb.)
Actuator Qty
42.00
1
42.00
1
42.00
1
42.00
1
42.00
1
180.00
1
180.00
1
180.00
1
180.00
1
180.00
1
180.00
1
180.00
1
180.00
1
180.00
2
180.00
2
180.00
2
180.00
2
180.00
3
180.00
3
CLCH-SVX07K-EN
No
No
No
No
No
No
No
No
No
No
No
No
No
No