Section-To-Section Seam Cap Installation For Hurricane Units - Trane CSAA Installation, Operation And Maintenance Manual

Performance climate changer air handlers indoor and outdoor units sizes 3 to 120
Hide thumbs Also See for CSAA:
Table of Contents

Advertisement

17. Install the section-to-section screws inserting the
appropriate screws through the overlapping flanges
using a powered impact gun and taking care not to
strip the screws. Outdoor air handlers will ship with a
seam cap that is to be installed over the section-to-
section seams. Factory-supplied butyl tape must be
continuously applied over the top and both side
Figure 41. Section-to-section seam cap installation for hurricane units
See Detail A
Single Roof
See Detail B
CLCH-SVX07K-EN
Hurricane units
Double Roof
seams prior to seam caps being applied. See
Detail A and Detail B for hurricane units for sizes 3-120.
Detail C applies to non-hurricane units size 3-120 (see
Figure
43).
Detail A
Detail B
Butyl tape
Seam cap
Installation - Mechanical
Figure 41
Butyl tape
Seam cap
Butyl tape
Roof overhang
35