Installation - Mechanical
removed after they are joined. The exception to this rule is
for size 35-50 stacked units. For these sizes, the gussets
should be left in place for the lower level unit unless they
are installed in a shipping split that contains a coil. The
other exception is when access to install or change out
front-loaded filters is restricted or blocked.
Figure 27. Shipping gusset
Do not mistake the coil structural gusset (see
used on unit sizes 66-120 with the shipping gussets.
Figure 28. Coil structural gusset

Section-to-Section Assembly

Air handlers ship with all necessary assembly hardware
and gasket material. The hardware should be packaged in
either a clear plastic envelope or yellow bag inside the fan
section, access section, or mixing box.
The number of sections to be assembled often makes it
necessary to use more than one section to ship the
assembly material; therefore, check all sections
thoroughly before contacting your Trane sales
representative to report missing items.
Sections are joined with gasketing applied to one of the
mating surfaces and hardware to bolt the sections
together. The gasketing for section-to-section joints is a
closed cell foam with adhesive backing.
To assemble the unit:
1. Locate the mounting hardware and gasket material.
2. All shipping supports and crating on the face of the
sections must be removed and discarded to permit
proper fit-up and sealing of the surfaces. Remove any
30
shipping bolts located on the mounting surfaces of the
sections (see
Figure 29. Section-to-section installation
Indoor units - Gasket
0.375 in.T x 0.750 in.W (3-30)
1.0 in.T x 0.375 in.W (35-120)
Outdoor units - Butyl tape
Figure
28)
3. Apply the gasketing to one of the mating surfaces; see
Figure
Figure 30. Coil section-to-downstream section bolt up
Indoor units - Gasket
0.375 in.T x 0.750 in.W (3-30)
1.0 in.T x 0.375 in.W (35-120)
Note: Gasket/Butyl tape should be on outermost edge of
panel. See installation in
Figure
29).
add additional layer of Butyl tape
29,
Figure
30, and
Figure
with splash guard
Outdoor units - Butyl tape
add additional layer of Butyl tape
Figure 31
Butyl tape
0.375 in.T x 0.375 in.W
Indoor units (35-57 only)
0.375 in.T x 0.375 in.W
33.
0.375 in.T x 0.375 in.W
Indoor units (35-57 only)
0.375 in.T x 0.375 in.W
and
Figure 32
CLCH-SVX07K-EN