Trane Tr150 Switching Frequency; Trane Tr150 Vfd Programming Parameters - Trane CSAA Installation, Operation And Maintenance Manual

Performance climate changer air handlers indoor and outdoor units sizes 3 to 120
Hide thumbs Also See for CSAA:
Table of Contents

Advertisement

.
Table 38. Trane TR150 Switching Frequency
Horsepower
Voltage
0.5 - 15
208/230
20-60
208/230
0.5 - 30
460
40 - 125
460
0.5 - 10
575
15 - 125
575
Table 39. Trane TR150 VFD Programming Parameters
Parameter #
TR150
Description
0-03
Region
1-03
Torque Characteristics
1-20
Motor Power
1-22
Motor Voltage
1-24
Motor Current
1-25
Rated Motor Speed
1-71
Start Delay
1-73
Flying Start
1-90
Motor Thermal Protection
3-02
Minimum Reference
3-03
Maximum Reference
3-15
Terminal 53 Analog Input
3-41
Ramp-up Time
3-42
Ramp-down Time
4-12
Output Freq Low Limit
4-14
Output Freq High Limit
4-18
Current Limit
4-19
Max Output Frequency
5-12
Terminal 27 Digital Input
5-40
Function Relay
Terminal 53 Low Ref
6-14
Feedback
Terminal 53 High Ref
6-15
Feedback
14-01
Switching Frequency
14-20
Reset Mode
CLCH-SVX07K-EN
Max KHz
Trane Setting
16
16
12
12
16
16
12
12
12
12
8
8
Factory Default
International
Auto Energy Optim. VT
Depends on unit
Depends on unit
Depends on unit
Depends on unit
0.0 Sec
Disabled
ETR Trip 1 [4]
Application dependant
60Hz
Analog Input 53
Application dependant
Application dependant
Application dependant
60 or the Value of Maximum Inverter
Frequency (Hz) on nameplate if fan is direct drive.
Application dependant
Application dependant
No Operation
No Operation
0.0 Hz
Application dependant
5.0 kHz
Manual Reset
WARNING
Hazardous Voltage w/Capacitors!
Failure to disconnect power and discharge capacitors
before servicing could result in death or serious injury.
Disconnect all electric power, including remote
disconnects and discharge all motor start/run
capacitors before servicing. Follow proper lockout/
tagout procedures to ensure the power cannot be
inadvertently energized. For variable frequency drives
or other energy storing components provided by Trane
or others, refer to the appropriate manufacturer's
literature for allowable waiting periods for discharge of
capacitors. Verify with an appropriate voltmeter that all
capacitors have discharged.
For additional information regarding the safe discharge
of capacitors, see PROD-SVB06*-EN
Auto Energy Optim. VT [3]for Belt-Drive Fans
Variable Torque [1]for Direct-Drive Fans
Set Based on Motor Nameplate
Set Based on Motor Nameplate
Set Based on Motor Nameplate
Set Based on Motor Nameplate
60 or the Value of Maximum Inverter
Frequency (Hz) on nameplate if fan is direct drive.
60 or the Value of Maximum Inverter
Frequency (Hz) on nameplate if fan is direct drive.
65 Hz or 120 Hz for Direct Drive Fan
Relay 1 Active No Alarm [160]
Relay 2 Active Motor Running [5]
60 or the Value of Maximum Inverter
Frequency (Hz) on Nameplate if fan is direct drive.
Set to Max for HP (see
Start-Up
Trane Setting
North American
2 Sec
Enable
ETR Trip 1 [4]
0 Hz
Analog Input 53
30 Sec
30 Sec
20 Hz
110%
Coast Inverse
20 Hz
Table
38)
Automatic Reset x 5
129

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents