0H8: High Pressure Sensor Error - Carrier 38VMA Series Service Manual

Outdoor unit for variable refrigerant flow (vrf) heat pump system
Table of Contents

Advertisement

j. 0H8: High Pressure Sensor Error
1.
Error display:
ODU display: 0H8
2.
Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3.
Error definition:
4.
In the condition of unit operation or T4 > -10℃, when the detected HIGH PRESS < 0.3MPa lasts for 20 seconds, the high
pressure sensor fault is reported.
5.
Possible causes:
The high pressure error is caused by lack of refrigerant in the system
Damaged sensor
Damaged main board