b. Refrigerant Recycling Operation
"_n21" Refrigerant recycles to outdoor units
1.
Close the liquid stop valve.
2.
Enter "Refrigerant recycle to outdoor units (_n21)" mode.
3.
Let the unit run for a while, and then close the gas valve quickly.
"_n22" Refrigerant recycles to indoor units
1.
Close the liquid stop valve.
2.
Enter "Refrigerant recycle to indoor units (_n22)" mode.
3.
Let the unit run for a while, and then close the gas valve quickly.
"_n23" Refrigerant recycled to piping
Enter "Refrigerant recycle to piping (_n23)" mode and all indoor valves will open.
c. Snow-Blowing Function
1.
Press SW5 button on spot check box of the header outdoor unit to enter the snow-blowing function.
It will display"Sn0" for 15 seconds.
2.
Press SW5 button again to exit the snow-blowing function.
It will display "Sn1" for 15 seconds.
The snow-blowing modes can be selected through S11 dip switch on spot check box.
Mode
S11
If the unit receives a startup signal, it will exit the snow-blowing function.
Heavy Snow Mode
Light Snow Mode