0P1: Current Leakage Error - Carrier 38VMA Series Service Manual

Outdoor unit for variable refrigerant flow (vrf) heat pump system
Table of Contents

Advertisement

p. 0P1: Current Leakage Error
1.
Error display:
ODU display: 0P1
2.
Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3.
Error definition:
Current leakage on ODU > 90–100mA and LED1 flashes on the leakage protection board.
4.
Possible causes:
Abnormal insulation resistance and leakage for unit parts
Damaged leakage current transformer
Damaged main board
55