0F6: Electronic Expansion Valve Error; 10Hd 20Hd: Follower Unit Error - Carrier 38VMA Series Service Manual

Outdoor unit for variable refrigerant flow (vrf) heat pump system
Table of Contents

Advertisement

n. 0F6: Electronic Expansion Valve Error
1.
Error display:
ODU display: F6
2.
Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3.
Error definition:
Abnormal feedback signal detected for the electronic expansion valve in the system.
4.
Possible causes:
Solenoid coil for electronic expansion valve is installed incorrectly
Improper wiring of the solenoid coil for electronic expansion valve
Damaged electronic expansion valve or solenoid coil
Damaged main board
o. 10Hd 20Hd: Follower Unit Error
1.
Error display:
ODU display: 10Hd 20Hd (displayed on header unit only)
2.
Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3.
Error definition:
Error on follower unit is reported on the header unit.
4.
Possible causes:
Error on follower unit
54