0E5: Voltage Protection - Carrier 38VMA Series Service Manual

Outdoor unit for variable refrigerant flow (vrf) heat pump system
Table of Contents

Advertisement

d. 0E5: Voltage Protection
1.
Error display:
ODU display: 0E5
2.
Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3.
Error definition:
Voltage of the ODU is not within the acceptable range.
4.
Possible causes:
Improper voltage
Lack of power supply phase for the ODU
Improper wiring within electric control box
Damaged main board of ODU