0P4 0H6: Discharge Temperature Protection - Carrier 38VMA Series Service Manual

Outdoor unit for variable refrigerant flow (vrf) heat pump system
Table of Contents

Advertisement

t. 0P4 0H6: Discharge Temperature Protection
1.
Error display:
ODU display: 0P4/0H6
2.
Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3.
Error definition:
0P4 is reported when the maximum value registered for discharge temperature sensor on the main board is > 239°F.
0H6 is reported when 0P4 occur 3 times within a 100 minute period.
4.
Possible causes:
High discharge temperature caused by lack of refrigerant in the system
Damaged sensor
Damaged main board
Lack of spray cooling function caused by a spray valve improper operation
Low pressure resulting from refrigerant blockage on the high pressure side due to solenoid valve error (IDU, ODU)
59