0P2 0H5: Low Pressure Protection - Carrier 38VMA Series Service Manual

Outdoor unit for variable refrigerant flow (vrf) heat pump system
Table of Contents

Advertisement

r. 0P2 0H5: Low Pressure Protection
1.
Error display:
ODU display: 0H5/0P2
2.
Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3.
Error definition:
0P2 error is reported when the registered value of low pressure sensor on the main board is < 1.45 psi.
0H5 error is reported when 0P2 occurs 5 times with in a period of 100 minutes.
4.
Possible causes:
The low pressure error is caused by lack of refrigerant in the system
Damaged sensor
Damaged main board
Low pressure because of refrigerant blockage on the high pressure side due to improper operation of the solenoid valve
(IDU, ODU)
57