Table 36 - Low Pressure Sensor Voltage Characteristics*
Resistance (KΩ)
Low pressure (psi)
14.5
16.0
17.4
18.9
20.3
21.8
23.2
24.7
26.1
27.6
30.5
31.9
33.4
34.8
37.7
39.2
42.1
43.5
46.4
47.9
50.8
53.7
55.1
58.0
60.9
63.8
66.7
69.6
72.5
75.4
78.3
81.2
84.1
88.5
91.4
94.3
* Outdoor unit: Low pressure sensor
Output voltage(V)
49.51
0.70
47.91
0.72
46.40
0.74
44.97
0.76
43.61
0.78
42.31
0.80
41.09
0.82
39.92
0.84
38.80
0.86
37.73
0.88
35.74
0.92
34.81
0.94
33.92
0.96
33.06
0.98
31.45
1.02
30.69
1.04
29.25
1.08
28.58
1.10
27.29
1.14
26.68
1.16
25.52
1.20
24.44
1.24
23.92
1.26
22.94
1.30
22.015
1.34
21.14
1.38
20.32
1.42
19.54
1.46
18.81
1.50
18.11
1.54
17.45
1.58
16.82
1.62
16.22
1.66
15.37
1.72
14.84
1.76
14.33
1.80
Resistance (KΩ)
Output voltage(V)
13.61
1.86
13.15
1.90
12.50
1.96
11.89
2.02
11.50
2.06
10.95
2.12
10.43
2.18
9.93
2.24
9.46
2.30
9.02
2.36
8.59
2.42
8.19
2.48
7.81
2.54
7.32
2.62
6.98
2.68
6.54
2.76
6.23
2.82
5.84
2.90
5.46
2.98
5.20
3.04
4.86
3.12
4.53
3.20
4.23
3.28
3.93
3.36
3.59
3.46
3.32
3.54
3.07
3.62
2.77
3.72
2.54
3.80
2.27
3.90
2.01
4.00
1.77
4.10
1.53
4.20
1.31
4.30
1.10
4.40
0.89
4.50