b. 0E2: Communication Error Between ODU and IDU
1.
Error display:
ODU display: 0E2
2.
Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3.
Error definition:
Communication Error between ODU and IDU
4.
Possible causes:
Communication lines between ODU and IDU are installed incorrectly
Improper power supply for IDU
Damaged communication adapter and main board of ODU
Communication line over 3937 feet
External interference (e.g. electromagnetic )
Communication Terminal Block of ODU