Instruction For Advanced Mode - Carrier 38VMA Series Service Manual

Outdoor unit for variable refrigerant flow (vrf) heat pump system
Table of Contents

Advertisement

List of Advanced Mode Codes
Table 32 -
Symbol
_n1_
Special function for debug
_n2_
Refrigerant recycle function
_n3_
_n4_
_n5_
Silent mode setting
_n8_
Static pressure mode setting
_nb_
Temperature unit setting
T4 sensor (outdoor temperature) threshold
to enable Auxiliary Heat. Aux heat will
_NC_
enable when outdoor temperature falls 1.8 F
below this temperature.
NOTE: All codes are only available for master unit.
a. Instruction for Advanced Mode
Special function for debug:
"_n12" Forced Cooling
Enter "Forced cooling (_n12)" mode. All indoor units will run in cooling mode, and the forced cooling mode will be exited
automatically after running 60 minutes.
"_n13" Forced Heating
Enter "Force heating (_n13)"mode. All indoor units will run in heating mode, and the forced heating mode will be exited
automatically after running 60 minutes.
Function
Error query
Night time setting
Item
_n12
Forced cooling (62.6⁰F of IDU)
_n13
Forced heating (86⁰F of IDU)
_n14
Cooling test
_n15
Heating test
_n21
Refrigerant recycle to outdoor units
_n22
Refrigerant recycle to indoor units
_n23
Refrigerant recycle to piping
_n26
Maintenance operation
_n31
Historical error query
_n32
Clear the historical errors
_n41
6/10h (default)
_n42
6/12h
_n43
8/10h
_n44
8/12h
_n51
Night silent mode
_n52
Silent mode
_n53
Super silent mode
_n54
None silent mode (default)
_n81
Standard static pressure mode (Default)
_n82
Low static pressure mode (Reserved)
_n83
Medium static pressure mode (Reserved)
_n84
High static pressure mode (Reserved)
_nb1
Temperature unit: °C
_nb2
Temperature unit: °F (Default)
_nC1
Auxiliary heat disabled
_nC2
5°F
_nC3
15°F
_nC4
25°F
_nC5
35°F
_nC6
45°F
_nC7
55°F
_nC8
65°F