g. 0H1: Communication Error Between Main Control Chip and Communication Chip
1.
Error display:
ODU display: 0H1
2.
Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3.
Error definition:
Communication fault of main control chip IC55 and communication chip IC33 on main board.
4.
Possible causes:
Improper power supply
Damaged transformer
Damaged main board
h. 0H2~0H3: Incorrect Number of ODUs
1.
Error display:
ODU display: 0H2 or 0H3 (displayed on header unit only)
2.
Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3.
Error definition:
0H2 -- The number of physical connected follower units to master unit is less than ENC1 rotary switch setting.
0H3 -- The number of physical connected follower units to master units is more than ENC1 rotary switch setting.
4.
Possible causes:
Improper power supply for ODU
Duplicated address setting for ODU
Communication lines between ODUs are installed incorrectly
Damaged communication terminal block or main board for ODU