Capacity Range - Carrier 38VMA Series Service Manual

Outdoor unit for variable refrigerant flow (vrf) heat pump system
Table of Contents

Advertisement

Table 1 – Indoor Unit Capacity Chart
Connectable Indoor Unit Capacity
Index *
Outside air
4-way cassette
Compact 4-way cassette
High wall
Low static duct
Medium static duct
High static duct
Vertical AHU
Underceiling/floor
Floor console recessed
* For example: The capacity index of 40VMF009---3 and 40VMV024 is 9 and 24 respectively.

2. Capacity Range

Connected capacity ratio =
Table 2 - Connected Capacity Ratio
Keep a proper connected capacity ratio for the entire system.
Min. combination ratio
50%
NOTES
*1
When 40VMH048, 054, 072, 096---3 is installed.
*2
When outside air units (40VMA) and standard indoor units are connected, the total capacity index of the 40VMA must be
limited to 30% or less of the capacity index of the outdoor unit.
*3
When the total capacity of 40VMH048, 054, 072, 096---3 or 40VMV exceeds 30%, the combination must not exceeds 100%.
7
9
40VMA
40VMF
40VMC
40VMW
40VML
40VMM
40VMH
40VMV
40VMU
40VMR
Total capacity index of the indoor units
Capacity index of the outdoor units
40VMH for all IDUs *1 ,
40VMV for all IDUs
100%
12
15
18
24
Max. combination ratio
40VMA connected with
other IDUs
100% *2
30
36
48
At least one 40VMH *1 or
40VMV connected
130% *3
54
72
96
Other indoor unit
models
135%
5