Carrier 38VMA Series Service Manual page 25

Outdoor unit for variable refrigerant flow (vrf) heat pump system
Table of Contents

Advertisement

Table 9 - Outdoor unit heating capacity calculation
Outdoor Unit Capacity x 1000 BTU
72
96
120
144
QHo: Outdoor Unit Heating Capacity
QHo = QHi x D/∑D(Round number)
T2A correction factor E
T = 102⁰F (default)
QHr: Outdoor Unit Real Heating Capacity
QHr = QHo + E
For example:
Outdoor Unit 72 + 96,Heating Indoor Unit (12K x 6) + (18K x 6),T1 = 63⁰F,TS = 70⁰F,T4 = 45⁰F,T2A (average) = 93⁰F
T1 – TS = 63 – 70 = -7,so B = 2
T4 = 45,so C = 100%
T2A (average) = 93⁰F,so E = 6
QHi = ∑(AxB) x C =(1.2 x 2 x 6 + 2.0 x 2 x 6)x 100% = 38.4,Round number:39
72 outdoor unit capacity:QHo = QHix D / ∑D = 39 x 8 /(8 + 10)= 17.3,Round number:18
96 outdoor unit capacity:QHo = QHix D / ∑D = 39 x 10 /(8 + 10)= 21.6,Round number:22
72 outdoor unit actual capacity:QHr = QHo + E =18 + 6 = 24,From the frequency table:70Hz
96 outdoor unit actual capacity:QHr = QHo + E = 22 + 6 = 28,From the frequency table:78Hz
NOTES:
TS:
Indoor unit setting temperature
T1:
Room temperature
T2A:
Temperature of evaporator inlet
T2B:
Temperature of evaporator outlet
T4:
Ambient temperature
Outdoor Unit Capacity (HP) D
8
10
12
14
25