AtL: Ambient Temperature Limit Operation

1.
Error display:
ODU display: AtL ODU display only
2.
Applicable models:
38VMA***HDS5-1 (208/230V-3Ph-60Hz)
38VMA***HDS6-1 (460V-3Ph-60Hz)
3.
Error definition:
ODU operating outside the allowable limits (allowable limits: cooling 5~125FDB, heating -4~64FWB)
4.
Possible causes:
The ODU ambient temperature exceeds the allowable operational limit
Improper connection at the sensor terminal
Damaged ambient temperature sensor
Damaged main board
Caution: Turn off the power switch before connecting or disconnecting the connector. Failure to do so could damage
the board.
76