High Pressure Switch - Carrier PrimeLINE 69NT40-561-200 Operation And Service Manual

Container refrigeration units
Hide thumbs Also See for PrimeLINE 69NT40-561-200:
Table of Contents

Advertisement

DO NOT add any oil to the replacement compressor. Replacement compressor is shipped with full oil
charge of 60 oz.
13. Cut and discard the wire ties used to hold the base plate to the compressor.
14. Place the new SST washers on each side of the resilient mounts, and the new Mylar washer on the bottom
of it as shown in
Figure
15. Place the new Teflon seals at the compressor suction and discharge ports as well as the O-rings at the
unloader and economizer line connection ports. Hand tighten all four connections.
16. Torque the four base-mounting screws to 6.2 mkg (45 ft-lbs).
17. Torque the compressor ports / connections.
SERVICE VALVE / CONNECTION
Suction and Discharge Rotalocks
Unloader connection
Economized connection
18. Connect (butt-splice and heat shrink) the new compressor dome temperature sensor with the old sensor
wires removed in step 8. Wire-tie any loose wiring as appropriate.
19. Evacuate the compressor to 1000 microns if the unit was pumped down before the replaced compressor
was removed. Otherwise, evacuate the complete unit and charge it with refrigerant (see
Section
7.7.1).
20. Open the compressor terminal cover and connect the compressor power cable following the steps below:
a. Liberally coat the orange gasket surfaces with the Krytox lubricant.
b. Install the orange gasket part onto the compressor fusite with the grooved or threaded side out. Ensure
that the gasket is seated onto the fusite base.
c. Coat the inside of the power plug (female) connector pins with the Krytox lubricant, and insert the plug
onto the compressor terminal connections. Make sure, the orange gasket has bottomed out onto the
fusite and it fits securely onto the terminal pins while fully inserted into the orange plug.
d. Connect the green ground wire to the grounding tab located inside the terminal box of the compressor
using the self-tapping grounding screw. Close the compressor terminal box using the terminal cover
removed in step 20.
21. Backseat all service valves, connect the power to the unit and run it for at least 20 minutes.
22. Perform a leak check of the system.

7.10 HIGH PRESSURE SWITCH

7.10.1
Checking High Pressure Switch
1. Remove switch as outlined in
2. Connect ohmmeter or continuity light across switch terminals. Ohm meter will indicate no resistance or con-
tinuity light will be illuminated if the switch closed after relieving compressor pressure.
3. Connect hose to a cylinder of dry nitrogen (see
7.5. Install the four base mounting bolts loosely.
!
Do not use a nitrogen cylinder without a pressure regulator.
The high pressure switch is non-adjustable.
Figure
7.10.2.
NOTE
TORQUE VALUE
108.5 to 135.5 Nm (80 to 100 ft-lbs.)
24.5 to 27 Nm (18 to 20 ft-lbs.)
32.5 to 35 Nm (24 to 26 ft-lbs.)
WARNING
NOTE
Figure
7.6).
7–9
Section 7.6.1
and
T-362

Advertisement

Table of Contents
loading

Table of Contents