0H9 0P9: Dc Fan Protection - Carrier 38VMA Series Service Manual

Outdoor unit for variable refrigerant flow (vrf) heat pump system
Table of Contents

Advertisement

v. 0H9 0P9: DC Fan Protection
1.
Error display:
ODU display: 0H9 0P9
Display on line controller: 0H9 0P9
2.
Applicable models:
38VMA***HDS5-1
38VMA***HDS6-1
3.
Error definition:
Multiple errors related to ODU fan motor and fan motor driver.
Check whether the following are normal:
Fan motor of ODU
Fan board
Power supply of fan board
Signals between fan board and main board
4.
Possible causes:
Check wiring between the main board to the fan board, power lines from the power supply circuit to the fan board, wires
from the fan motor to the fan board
Check DIP-IPM screws on the fan board
Damaged power circuit of fan board
Damaged fan board
Damaged fan motor
Damaged main board