Power Cable Size
10 AWG
8 AWG
Install a circuit breaker to a rectifier (or power distributor) for the stable power.
The capacity of the circuit breaker is 25 A. (Use UL listed circuit breakers.)
Connecting Power Cable
To connect a power cable, do the following:
Prerequisites
Before proceeding with connecting the power cable, make sure that you have the
items mentioned in the table below:
Table 22.
Parts and Tools for Connecting Power Cable
Category
Installation Section
Cable
Minimum Cable bend Radius
Connector
Working Tools
The table below outlines the power cable connector pin map:
Table 23.
DC Power Cable/Connector Pin Map
Power Connector Pin Number
Pin 1
Pin 2
MT3204 Series Installation Manual v1.0
Copyright © 2018, All Rights Reserved.
Description
DC Distributor-MMU power input port
10 AWG × 2C, 8 AWG × 2C
Dynamic bend radius: 8 × OD
Static bend radius: 12 × OD
Distributor
Check specifications of DC distributor output terminal
per site and prepare fasteners.
MMU (DC)
JONHON, Push Pull Type, CT48J-1502TSCBM-07 to
OPEN
Cable Cutter
Wire Stripper
Compressor
Heating Gun
Nipper
Description
Color
-48 V DC
Red
RTN
Black
Chapter 3 Connecting Cables
Maximum Installation Length
TBD
TBD
Confidential